PL3000 Series Hardware Manual
5-6
Installation Requirements
For easier maintenance, operation, and improved ventilation, be sure to install the PL at least 50mm
[1.97in.] away from adjacent structures and other equipment. For the face to which the cable is connected,
however, a space of 120mm [7.72in.] or more is necessary for cable curve.
Be sure that the ambient operation temperature and the ambient humidity are within their designated
ranges. When installing the PL on the panel of a cabinet or enclosure, “Surrounding air temperature” indi-
cates both the panel face and cabinet or enclosure’s internal temperature.
Be sure that heat from surrounding equipment does not cause the PL to exceed its standard operating tem-
perature.
When installing the PL in a slanted panel, the panel face should not incline more than 30°.
When installing the PL in a slanted panel, and the panel face inclines more than 30°, the surrounding air
temperature must not exceed 40°C. You may need to use forced air cooling (fan, A/C) to ensure the sur-
rounding air temperature is 40°C or below.
The PL Series unit does not support longitudinal mounting.
120 [4.72]
Unit: mm [in.]
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
30mm
[1.18in]
50mm
[1.97in]
Panel Face
30mm
[1.18in]
Cabinet interior
30° or less