PL3000 Series Hardware Manual
5-26
Wiring
When connecting the power cord, use the following items. (Made by Phoenix Contact
*1
.)
Power Connector (Right-angle Screw) Specifications
Connecting the Power Cord
(1) Confirm that the power is not supplied to the PL unit.
(2) Loosen three screws in the center of the power connector.
(3) Strip the membrane of the power cord, twist the wire ends, and connect them to the power connector.
(4) Attach the Power Connector to the PL and fix it to the PL main unit with right/left tightening screws.
Recommended Driver SZF 1-0.6x3.5 (1204517)
Recommended Pin Terminals
AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)
Recommended Pin Terminal Crimp Tool CRIMPFOX ZA3 (1201882)
*1 For details, please contact your local Phoenix Contact distributor.
+24V
− 0V
FG
FG Grounding Terminal connected to
the PL
• Use a flat-blade screwdriver (Size 0.6 X 3.5) to tighten the terminal screws.
The torque required to tighten these screws is 0.5 to 0.6 N•m [5-7 lb•in.].
• Do not solder the cable connection. Doing so may damage the unit due to
abnormal heat or cause a fire.
FG
−
+
Insertion
Direction
+
−
FG